Siemens inverter MM420 reported fault code - Solutions - Huaqiang Electronic Network

Probe high frequency needle JTK-50L-Q has 5 needles in the high frequency needle
Brand AVX TPSE226M035R0125 Low impedance tantalum capacitor AVX 22
Electronic scale crystal oscillator 3.2*2.5mm 3225 16M (16.000MHZ) 12PF 10PPM 20PPM 30PPM
Photocoupler

Siemens inverter MM420 reported no fault F0000 at all. The following is the fault code for all Siemens inverter MM420.
Possible causes of failures, fault diagnosis, and measures to be taken
F0001
Overcurrent
? The power of the motor does not correspond to the power of the inverter
? Wire short circuit of the motor
? Have ground fault check the following items
1. The power of the motor P0307 must be the power of the inverter P0206
Corresponding
2. The length of the cable must not exceed the maximum allowed
3. There must be no short circuit or ground fault in the cable and motor of the motor.
4. The motor parameters of the input inverter must correspond to the actual motor parameters used.
5. Enter the inverter's stator resistance value P0350 must be correct
6. The cooling air duct of the motor must be unobstructed and the motor must not be overloaded.
? Increase the ramp time
? Reduce the value of the increase
Off2
F0002
Overvoltage
? The voltage of the DC link r0026 exceeds the trip level P2172
? Overvoltage due to excessive supply voltage or motor in regenerative braking mode
? The slope drops too fast or the motor is rotated by a large inertia load and is under regenerative braking. Check the following items.
1. The power supply voltage P0210 must be within the range specified on the inverter nameplate.
2. The DC link voltage controller must be valid P1240 and correctly parameterized
3. The ramp-down time P1121 must match the inertia of the load
Off2
F0003
Undervoltage
? Power supply failure
? The impact load exceeds the specified limit value. Check the following items.
1. The power supply voltage P0210 must be within the range specified on the inverter nameplate.
2. Check if the power supply is short-circuited or there is a transient voltage drop.
Off2
F0004
Inverter over temperature
? Cooling fan failure
? The ambient temperature is too high Check the following items
1. The cooling fan must be running normally when the inverter is running.
2. The frequency of the modulation pulse must be set to the default value.
3. The inlet and outlet of the cooling duct must not be blocked. The ambient temperature may be higher than the allowable value of the inverter.
Off2
F0005
Inverter I2 t over temperature
? Inverter overload
? Work/stop gap cycle time does not meet the requirements
? Motor power P0307 exceeds the load capacity of the inverter P0206
Check the following items
1. The duty/stop gap cycle time of the load must not exceed the specified allowable value.
2. The power of the motor P0307 must be the power of the inverter P0206
Match
Off2
Troubleshooting
MICROMASTER 420 uses Daquan 6-4
Possible causes of failures, fault diagnosis, and measures to be taken
F0011
Motor I2 t over temperature
? Motor overload
? Motor data error
• Run at low speed for a long time to check the following items
1 Check the motor data should be correct
2 Check the load of the motor
3 Lifting setting value P1310 P1311 P1312 too high
4 The heat transfer time constant of the motor must be correct
5 Check the motor's I2 t over temperature alarm value
Off1
F0041
Motor stator resistance automatically detects fault
? Motor stator resistance automatically detects fault 1 Check if the motor is properly connected to the inverter
2 Check if the motor data of the input inverter is correct.
Off2
F0051
Parameter EEPROM
malfunction
• A read/write error occurs when storing non-volatile parameters 1 Perform a factory reset and re-parameterize
2 Replace the inverter
Off2
F0052
Power component failure
• An error occurred while reading the parameters of the power component or the data was illegally replaced by the inverter Off2
F0060
Asic timeout
? Internal communication failure 1 Confirm the existing fault
2 If the fault occurs repeatedly, please replace the inverter.
Off2
F0070
CB setpoint failure
• The set value cannot be received from the CB communication board at the end of the communication message
1 Check the wiring of the CB board
2 Check the communication master station
Off2
F0071
At the end of the message
USS RS232-
No data on the link
• Cannot be taken from USS BOP at the end of the communication message
The link gets a response
1 Check the wiring of communication board CB
2 Check the USS master station
Off2
F0072
At the end of the message
USS RS485
No data on the link
• Cannot be from USS COM at the end of the communication message
The link gets a response
1 Check the wiring of communication board CB
2 Check the USS master station
Off2
F0080
ADC input signal loss
? Broken line
? The signal exceeds the limit value. Check the wiring of the analog input. Off2
F0085
External fault
? External fault block triggered by the terminal input signal triggers the faulty terminal input signal Off2
F0101
Power component overflow
• Software error or processor failure 1. Run the self test program
2. Replace the inverter
Off2
F0221
PID feedback signal is below the minimum
? The PID feedback signal is lower than the minimum value set by P2268
1. Change the setting value of P2268
2. Adjust the feedback gain factor
Off2
F0222
PID feedback signal is higher than the maximum
• The PID feedback signal exceeds the maximum value set by P2267
1. Change the setting value of P2267
2. Adjust the feedback gain factor
Off2
F0450
BIST test fault fault value
1 Some power components have failed testing
2 Some control board tests are faulty
4 Some functional tests are faulty
8 Some I/O modules have a test failure and only refer to MM.
420
16 Internal RAM is faulty during power-on detection
1. The inverter can run but some functions do not work correctly
2. Replace the inverter

Headphones

We've been around for over 16+ years. We make sure our sound is The Best Sound.
Our products include gaming headset, Bluetooth Earphone, Headphones Noise Cancelling, Best Wireless Earbuds, Bluetooth Mask, Headphones For Sleeping, Headphones in Headband, Bluetooth Beanie Hat, bluetooth for motorcycle helmet, etc
Manufacturing high-quality products for customers according to international standards, such as CE ROHS FCC REACH UL SGS BQB etc.
We help 200+ customers create custom Bluetooth headphones, earbuds, earphones, etc audio products design for various industries.

Customized Headphones, personalized gifts, promotional products custom , Bluetooth Earphones,Best Headphones

TOPNOTCH INTERNATIONAL GROUP LIMITED , https://www.itopnoobluetooth.com